Sunday, June 27, 2010

Hannah Montana Encuera



high efficiency heat pump for heating, electrical characteristics and estimates of consumption

Question, *** Contributed by gsa @ libero.it, 26 06 2010
Hello, I'm a customer who in April I bought the solar panel, solar disk for the new house. This time I would bother to ask for advice. I am writing because I recently purchased 2 conditioning heat pump class AA double Daikin FTYN35GX and FTYN50GX like those I saw on the vs site, but I could not use them to do well for heating. When the outside temperature goes below 10 degrees feels a significant decrease in performance and are forced to turn on the boiler. In the new house are in the process of preparing the new heating system. I heard a lot of good high efficiency heat pumps for heating do winter, but I did not understand what they are and what characteristics must possess? I would not make the mistake of buying products not suited to heating degree I would be if I set out what are the features to find the best cars and how do I calculate the cost of the heat pump compared with the boiler plant. Regards Sav Thurs *** ***

response, sent by ecotecna@gmail.com, 29 06 2010
Ecotecno - Dear Sav Thurs *** *** regards Daikin air conditioners that you mentioned, such models on / off in this case, to make warming winter you had to use two size instead of 18000 BTU and 12000 BTU 24000 BTU 18000 BTU's instead. In other words you have purchased air conditioners to make the heat required in winter it is always recommended to be oversized, but at this point it is clear that the power consumption becomes so high that the spending bill can match that of the gas and you lose the convenience.

We come to reply on high efficiency heat pumps for a real winter heating. We will try to give an answer that might be useful to all those who want to do with this heating technology to reduce energy costs.

First, it is important to point out that everyone in the room air conditioners are Class AA, but very few people with the characteristics of high efficiency for heating, so the energy class AA does not say anything about the convenience for the winter heating .

features on which to focus attention are: a high COP at partial loads , a large air flow and minimal absorption is very low.

For example, a 9000 BTU air conditioner for winter heating should have:
  1. A COP (WC / Wa) at least a partial load of 7.50, leaving in the tables that matches the value in standard conditions and may be fictitious.
  2. The minimum flow rate must be greater than 6.5 cm / min. heating mode.
  3. absorption minimum must be less than 150 W (0.150 kW) in heating mode.
These three features are essential for create a real energy savings that will result in an economic benefit.

Calculations of energy efficiency (this paragraph has a more technical content, for those who lack knowledge of math you should skip to the section of the estimate of expenditure ....)
Let consider a high efficiency heat pump with 10000 BTU of power at partial load can deliver about 3300 W / h of heat absorption of about 0.44 kWh of electricity. Considering that on average in a domestic environment requires at least 45 W / m for a comfortable interior temperature of 20 ° C, then the unit will be heated a room of 3300/45 = 73.33 cubic meters in the case of a local height of 2.7 m corresponding to a surface of about the same 73.33 / 2.7 = 27.16 square meters. So, to heat a square meter dwelling you should consume about 0.44 / 27 = 0.0162 kWh of electricity per square meter .
With a system with radiators to heat a room of 50 square meters with a height of 2.70 m takes about 0.30 m³ / h natural gas is approximately 0.30 / 50 = 0 , 0060 mc / h of gas per square meter of usable area .

At this point should be taken into account Prices in the bill for electricity and natural gas, the best way is to add the kWh and cubic meters for the last 6 or 7 bills and divide by the total expenditure. This will easily get the average price per kWh of electricity and cubic meter of gas, including all taxes, incidental expenses, the rent etc..

From the data of our customers in Campania we got a average price of € 0.166 / kwh electric than average price of € 1.01 per cubic meter of gas .

Therefore with high efficiency heat pumps alimentate elettricamente a parità di condizione si può riscaldare un metro quadro di abitazione con una spesa di 0,166x0,0162= 0,0026 €/mq .
Con un impianto a termosifoni si può riscaldare un metro quadro di abitazione con una spesa di 1,01x0,0060= 0,0060 €/mq .

Stima della spesa in bolletta
Per cui nell'ipotesi di dover riscaldare quattro locali per un totale di 90 mq per 150 giorni all'anno per sole 4 ore al giorno nel caso dell'impianto di riscaldamento a gas la spesa prevista sarebbe di circa € 324.00 , using heat pumps would be spending € 140.40 .
If we are in presence of 6 rooms for a total of 150 sq m heated to 180 days per year for 8 hours a day, with the expense of gas boiler would € 1296.00 for the spending the same conditions with high efficiency air conditioners would € 516.00 .

course, these machines should be carefully chosen and well-dimensioned considering in what locations is convenient to install than installing a traditional heating system. So I would see that we should send a plan indicating which local housing aims to provide a heat pump and as a radiator. Can send faxes to the plan 0823/1780109, thanks.

Saturday, June 26, 2010

Hentay High Definition

heat pump high efficiency condensing boiler 100 kw

condensing boiler with centralized power greater than 100 kW in condominiums with more than four apartments

Ecotecno - I have not fully grasped the meaning of his question. Who has advised against the condensing boiler?

In some regions it is no longer allowed to move from centralized autonomy in buildings with more than four apartments (there are exceptions, however, and alternative routes) .
Maybe you're in the position of having to replace the old central boiler with a new one?

The rule for the tax refund of 55% of ALL COSTS when you install a condensing boiler, provides only a simplified procedure for boilers under 100 kW. For a true engineer heating engineer or surveyor with a minimum knowledge of even the procedure for boilers above 100 kW is feasible.
Perhaps those who have advised against the condensing boiler is not eligible for the procedure or the knowledge of 55% for boilers over 100 kW?


----- Original Message ----- From: rob @ fastwebnet.it *** Posted: Saturday, June 26, 2010 11:55
A: info@caldaie-climatizzatori.com Subject: FAQ - Contact Form from boiler-climatizzatori.com
This email was sent from the site www.caldaie-climatizzatori.com

Why is not recommended to replace the traditional communal heating boiler with the condensation in a building with> 4 apartments and / or power> 100 kw?

Garrison Motion Sensor

Gazelle Fondital flue

CHIMNEY FLUE FOR GAZELLE THECNO PREMIX

Ecotecno - radiators gas Fondital Gazelle THECNO Premix New S, that may appear on our website , are certified for emissions of NOx Class 5 , so you can install without flue pipe to the roof, but apart exhaust (exhaust pipe horizontal short) where the exhaust pipe is at least three feet from doors and windows.

From: *** ed @ tiscali.it Posted: Friday, June 25, 2010 17:52
A: info @ -boilers climatizzatori.com Subject: FAQ - Ecotecno

My name is Alberto. Gazelles are interested in the radiators. I live on the second floor of a 4-story building. I have to bring the exhaust gas to each radiator to the roof?

Thursday, June 24, 2010

La Braga Metalica Online



which are already finished but do not feel like you overcome by sleep,
do not want to give it up to boredom.
those nights when looking for an emotion behind the pixels,
looking for something that is still able to turn you on.
try to escape this heat of freezing.
try to distract you for a moment,
make you surprised by anything.
or is it just scrape
air from an empty barrel.
Today I realized how once women made me dream.
but because they are worse.

Saturday, June 19, 2010

Patchs Port Royale 2 1.1.0.89

those evenings of music

I steal a bit of space to spread an initiative created by me and some friends because of our collaboration with a local organizing live concerts and parties also have a certain thickness.

S is a petition, the found here or directly here


http://www.firmiamo.it/firmaperlamusica

absurd policy exists in many municipalities that prohibit the display "live" after midnight. as a result of what happened last Sunday (details here)
we mobilized for more rules and less fascist Tolerance.
The answer is already incredible and above our expectations.
If you want to help me out I shall be grateful.

Wednesday, June 9, 2010

Mqrio Salieri For Free

deja vu. Cut to three days if

elusive, mocking a grazed
percepire impotente
un presente imprendibile.
il pensiero legato
non affonda il colpo
non sviluppa in comprensione.
un soffio
mi disinnesco
in acquolina cerebrale
invano ancora
inseguo in affanno
lampi già chiusi
al sicuro nelle porte.
cado e finisco
sbriciolato sui gradini.

Thursday, June 3, 2010

Entocort More Drug_warnings_recalls



Sono ufficialmente esaurito.
però domani vado QUI e ci resto fino a domenica.
spero di tornare minimamente rigenerato.
se passate di lì fatevi riconoscere. sarò quello basso magro con una invidiabile pancetta da abuso di Spritz e mi aggirerò con il mio socio basso coi rasta e gli occhi azzurri.
I think it will be hard being away from wineries, but oh well, even if they are still committed to leave.